4230-T120-K0DE-35A The E-T-A 4230-T120-K0DE-35A is a 2-pole thermal magnetic miniature circuit breaker. It features a 35A current rating and supports up to 480VAC or 125VDC.
Mfr Part #:

4230-T120-K0DE-35A

Mfr Name: ETA
ETA
The E-T-A 4230-T120-K0DE-35A is a 2-pole thermal magnetic miniature circuit breaker. It features a 35A current rating and supports up to 480VAC or 125VDC.
Stock on Request

4230-T120-K0DE-35A Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Breaker Type
Current Rating
Current Rating (Amps)
Illumination
Mounting Type
Number of Poles
SVHC Present
Terminal Type
Voltage Rating

4230-T120-K0DE-35A Description

Short technical summary and product information.

The E-T-A 4230-T120-K0DE-35A is a thermal-magnetic miniature circuit breaker designed for reliable circuit protection. It conforms to EN 60947-2, UL 1077, and UL 489 standards, offering a high rupture capacity of up to 10,000 A.

 

This 2-pole breaker has a current rating of 35A and can operate at voltages up to 480VAC or 125VDC. It features screw terminals for connection and is designed for DIN rail mounting, making it suitable for various industrial and telecommunications applications.

 

Key specifications include an operating temperature range of -35°C to +70°C and an IP20 degree of protection. The breaker is built for durability with a mechanical life of 20,000 cycles and an electrical life of 6,000 cycles.

4230-T120-K0DE-35A Quick Information

Product Type: Circuit Breaker
Series: 4230-T
Canonical Name: E-T-A 4230-T Series Thermal-Magnetic Miniature Circuit Breaker
Subcategory: Thermal Magnetic

4230-T120-K0DE-35A Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

4230-T120-K0DE-35A Features

  • 2-pole thermal magnetic circuit breaker.
  • 35A current rating.
  • 480VAC / 125VDC voltage rating.
  • DIN rail mounting.
  • High rupture capacity.

4230-T120-K0DE-35A Applications

  • Protects cables, motors, and transformers.
  • Suitable for power supplies.
  • Used in industrial process control.
  • Ideal for telecommunications equipment.

4230-T120-K0DE-35A FAQs

5 frequently asked questions generated from this part’s specifications.
What is the voltage rating of the 4230-T120-K0DE-35A?

Under IEC/EN 60947-2, the breaker is rated AC 240 V (1-pole), AC 415 V (2-pole), DC 80 V (1-pole), and DC 125 V (2-pole in series). Under UL 1077: AC 277 V (1-pole), AC 480Y/277 V (2-pole), DC 60 V (1-pole), DC 125 V (2-pole). Under UL 489: AC 120 V (1-pole), AC 240 V (2-pole), AC 277 V (1-pole up to 32 A), AC 480Y/277 V (2-pole up to 32 A), DC 60 V (1-pole), DC 125 V (2-pole).

What is the operating temperature range?

The ambient operating temperature range is -35°C to +70°C.

What is the interrupting capacity?

The interrupting capacity is 10,000 A under UL 489 and IEC/EN 60947-2 (Icu), and 7,500 A under IEC/EN 60947-2 (Ics).

What mounting type does this breaker use?

It mounts on DIN rail.

What terminal type and wire size does it accept?

It has screw terminals accepting cables up to 35 mm², with a stripping length of 14 mm and tightening torque of 2 Nm.