| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Ambient Temperature | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Terminal Type | |
| Voltage Rating |
The E-T-A 4230-T110-K0DE-15A is a thermal-magnetic miniature circuit breaker (MCB) designed for reliable protection in various applications. It conforms to EN 60947-2, UL 1077, and UL 489 standards, ensuring broad applicability.
This single-pole breaker offers a current rating of 1.5A and supports AC voltage ratings up to 277V and DC voltage ratings up to 60V. It features a thermal-magnetic trip mechanism for robust circuit protection. The breaker is designed for DIN rail mounting, facilitating easy installation in control panels and electrical enclosures.
Key specifications include a rupture capacity of 10,000 A (AC/DC) and an impulse withstand voltage of 4kV. The operating ambient temperature range is -35°C to +70°C, making it suitable for diverse environmental conditions. The terminals are screw-type, with a recommended tightening torque of 2 Nm and support cable cross-sections up to 35 mm².
Typical applications include the protection of cables, motors, generators, transformers, thyristors, silicon rectifiers, computers, industrial process control systems, telecommunications equipment, and power supplies. Its robust construction and high rupture capacity ensure dependable operation.
For UL1077 applications (1-pole): 277VAC or 60VDC. For UL489 (1-pole): 120VAC, 277VAC or 60VDC. For IEC/EN 60947-2 (1-pole): 240VAC or 80VDC.
The interrupting capacity (Icu) is 10,000A AC/DC per IEC/EN 60947-2 and UL 489. The service breaking capacity (Ics) is 7,500A AC and 10,000A DC.
The ambient temperature range is -35°C to +70°C.
It mounts on DIN rail.
Screw terminals with a maximum tightening torque of 2 Nm and a stripping length of 14 mm. The maximum cable cross section is 35 mm².
It is approved under UL 1077, UL 489, and CSA C22.2 No 235.
It is a 1-pole device.