3VA6225-5HN31-2AA0 The Siemens 3VA6225-5HN31-2AA0 is a 3-pole molded-case circuit breaker with a 250A current rating and a 35kA breaking capacity at 480V. It features ETU350 LSI overcurrent protection.
Mfr Part #:

3VA6225-5HN31-2AA0

Mfr Name: Siemens
Siemens
The Siemens 3VA6225-5HN31-2AA0 is a 3-pole molded-case circuit breaker with a 250A current rating and a 35kA breaking capacity at 480V. It features ETU350 LSI overcurrent protection.
Stock on Request
$ Price Range: $0.99

3VA6225-5HN31-2AA0 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Connection Type
Current Rating (Amps)
Illumination
Mounting Type
Number of Poles
Overload Protection
Voltage Rating

3VA6225-5HN31-2AA0 Description

Short technical summary and product information.

This Siemens 3VA6225-5HN31-2AA0 is a molded-case circuit breaker designed for system protection. It is a 3-pole unit with a rated current of 250A and a breaking capacity of 35kA at 480V, compliant with UL 489 standards. The circuit breaker utilizes an ETU350 electronic trip unit with LSI (Long-time, Short-time, Instantaneous) protection functions.

 

Key electrical specifications include an insulation voltage of 600V and a maximum power loss of 42W. The mechanical service life is rated at a typical 20,000 switching cycles, with electrical endurance varying based on voltage and load conditions. The unit is designed for DIN rail mounting and has dimensions of 7.8 inches in height, 4.1 inches in width, and 3.4 inches in depth.

 

Additional features include HACR type compliance and a 100%-rated breaker marking according to UL 489. The adjustable overload protection ranges from 100A to 250A, and short-circuit protection is adjustable from 1.5 to 10 times the overload setting (Isd) and 10 times the rated current (Ii).

3VA6225-5HN31-2AA0 Quick Information

Product Type: Molded-case circuit breaker
Canonical Name: Siemens 3VA6 Molded-case circuit breaker, 3-pole, 250A, 600V, 35kA @ 480V
Subcategory: Molded Case Circuit Breaker

3VA6225-5HN31-2AA0 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3VA6225-5HN31-2AA0 Estimated Pricing

Qty Low High
1+ $0.99 $0.99

Estimated market price range - modelled values for guidance only, not live distributor offers.

3VA6225-5HN31-2AA0 Features

  • 3-pole molded-case circuit breaker
  • 250A operational current rating
  • 35kA breaking capacity at 480V (UL 489)
  • ETU350 electronic trip unit with LSI protection
  • DIN rail mounting type

3VA6225-5HN31-2AA0 Applications

  • System protection applications
  • Industrial control panels
  • Power distribution systems
  • HVAC and refrigeration circuits

3VA6225-5HN31-2AA0 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the current rating of the Siemens 3VA6225-5HN31-2AA0 circuit breaker?

The operational current rating is 250A at temperatures from 55°C to 70°C.

What is the breaking capacity of the 3VA6225-5HN31-2AA0 circuit breaker?

The breaking capacity according to UL 489 is 35kA at 480V, and according to IEC 60947, it is 55kA at 415V.

What type of overcurrent protection does the 3VA6225-5HN31-2AA0 circuit breaker offer?

It features an ETU350 electronic trip unit with LSI (Long-time, Short-time, Instantaneous) protection functions.

What is the insulation voltage rating for this circuit breaker?

The insulation voltage (Ui) is rated at 600V.

What are the physical dimensions of the Siemens 3VA6225-5HN31-2AA0?

The dimensions are 7.8 inches (198 mm) in height, 4.1 inches (105 mm) in width, and 3.4 inches (86 mm) in depth.

Is the Siemens 3VA6225-5HN31-2AA0 RoHS compliant?

The RoHS status is listed as RoHS3 Compliant.

What is the Moisture Sensitivity Level (MSL) for this component?

The Moisture Sensitivity Level (MSL) is 1 Unlimited.