This Siemens 3VA6210-5JT41-0AA0 is a 4-pole molded-case circuit breaker from the 3VA6 series, designed for system protection. It has a nominal current rating of 100A and an insulation voltage of 600V, with a maximum operational voltage of 690V.
The circuit breaker offers a breaking capacity of 35kA at 480V according to UL 489 standards, and 55kA at 415V according to IEC 60947 standards. It features an ETU556 electronic trip unit with LSI protection functions, allowing adjustable overload protection from 40A to 100A and short-circuit protection settings.
Designed for DIN rail mounting, this HACR Type circuit breaker is suitable for applications in heating, air conditioning, and refrigeration. It also includes communication functionality.
Key electrical endurance specifications include 6,000 switching cycles at AC-1 at 380/415V and 7,500 switching cycles at 600V. The mechanical service life is typically 20,000 switching cycles.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 100A at temperatures up to 70°C.
The insulation voltage is 600V, and the maximum operational voltage is 690V.
The breaking capacity is 35kA at 480V (UL 489) and 55kA at 415V (IEC 60947).
This circuit breaker is designed for DIN rail mounting.
It features LSI protection with adjustable overload protection from 40A to 100A and short-circuit protection settings.