| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage | |
| Voltage Rating | |
| Width |
The Siemens 3VA5222-6ED32-0AA0 is a molded-case circuit breaker from the SENTRON series, designed for system protection applications. This 3-pole breaker operates at a rated voltage of 690V AC and has an operational current rating of 225A at 40°C.
It offers a high breaking capacity, with a maximum short-circuit current (Icu) of 100 kA at 240V and 65 kA at 480V, according to IEC 60947 standards. The overcurrent release is of type TM210 with LI protection function. The breaker is suitable for HACR Type applications according to UL 489.
Mechanically, the unit has a service life of 20,000 switching cycles and features a DIN rail mounting type. Its dimensions are 185 mm in height, 105 mm in width, and 83 mm in depth, with a net weight of 2.192 kg.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 225A at 40°C.
The operating voltage is rated at 690 V AC.
The breaking capacity current according to UL 489 at 480 V is 65 kA.
This circuit breaker has 3 poles.
The mounting type is DIN Rail.