| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Connection Type | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Overload Protection | |
| Voltage | |
| Voltage Rating | |
| Width |
This Siemens 3VA5 series molded-case circuit breaker, part number 3VA5222-5ED32-1AA0, is designed for system protection applications. It operates at a rated voltage of 690V AC and features a 3-pole configuration.
The breaker has an operational current rating of 225A at 40°C, with overload protection set at Ir=225A and fixed short-circuit protection at Ii=10 x In. Its breaking capacity is 35kA at 480V, 85kA at 240V, and 18kA at 600V. The device includes HACR Type functionality.
With a mechanical service life of 20,000 switching cycles and electrical endurance ratings of up to 8,000 cycles, this circuit breaker is built for durability. It has a maximum power loss of 51W and an active power loss of 17.07W per pole. The dimensions are 185mm in height, 105mm in width, and 83mm in depth, with a net weight of 2.192 kg. It is designed for front connection with nut keeper kits on both ends, accommodating conductor cross-sections from 13 x 1 mm to 25 x 8 mm. The mounting type is DIN Rail.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage for this circuit breaker is 690 V AC.
The operational current rating is 225A at 40°C.
The breaking capacity is 35kA at 480V.
This circuit breaker has 3 poles.
The RoHS status is RoHS3 Compliant.
The Moisture Sensitivity Level is 1 Unlimited.
The REACH status is REACH Unaffected.