This Siemens 3VA5222-5EC61-0AA0 is a 2-pole molded-case circuit breaker from the 3VA5 UL frame 250 series, designed for system protection applications. It features a permanent rated current (Iu) of 225A, with operational current ratings varying from 225A at 40°C down to 197A at 70°C.
The circuit breaker has a maximum rated operational voltage of 690V AC and 500V DC, with an insulation voltage of 800V. It provides overload protection with an adjustable Ir of 225A and fixed short-circuit protection with an adjustable Ii range from 1125A to 2250A. The breaking capacity according to UL 489 is 35kA at 480V, and according to IEC 60947, it is 55kA at 415V.
With a mechanical service life of typically 20,000 switching cycles, the breaker is built for durability. Its dimensions are 185mm in height, 105mm in width, and 83mm in depth. The mounting type is DIN Rail, and the actuator type is a lever.
Key electrical specifications include a maximum power loss of 34.1W and an active power loss per pole of 17.07W. The electrical endurance at 380/415V is 8,000 switching cycles. This model is designated as HACR Type and has a UL file designation of MFAS.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage for this circuit breaker is 690 V AC and 500 V DC.
The breaking capacity according to UL 489 at 480V is 35 kA.
The permanent rated current (Iu) is 225 A.
This circuit breaker has 2 poles.
This circuit breaker supports DIN Rail mounting.
The dimensions are 185 mm in height, 105 mm in width, and 83 mm in depth.