This Siemens 3VA5 series molded-case circuit breaker, part number 3VA5220-7ED32-1AA0, is designed for system protection. It is a 3-pole breaker with a rated operational current of 200A at 40°C, derating to 167A at 70°C.
The breaker offers a significant breaking capacity of 100kA at 480V and 35kA at 600V, with a switching capacity class of C according to IEC 60947. It operates at a rated voltage of 690V AC and features TM210 overcurrent release with LI protection function.
Mechanically, the unit has a typical service life of 20,000 switching cycles. Its dimensions are 185mm in height, 105mm in width, and 83mm in depth. The breaker utilizes a front connection with a nut keeper kit for main current circuit connections, accommodating conductor cross-sections from 13 x 1 mm to 25 x 8 mm.
This circuit breaker is suitable for HACR Type applications according to UL 489. It has a maximum power loss of 43W, with an active power loss of 14.17W per pole at rated current in hot operating state.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage for this circuit breaker at AC is 690 V.
The breaking capacity of the 3VA5220-7ED32-1AA0 at 480V is 100 kA.
The operational current rating at 40°C is 200 A.
The typical mechanical service life of this circuit breaker is 20,000 switching cycles.
The dimensions are 185 mm in height, 105 mm in width, and 83 mm in depth.
This component is RoHS3 Compliant.
The Moisture Sensitivity Level (MSL) is 1 Unlimited.