| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Connection Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage | |
| Voltage Rating | |
| Width |
This Siemens 3VA5 series molded-case circuit breaker, part number 3VA5220-6ED32-1AA0, is engineered for robust system protection. It operates at a rated voltage of 690V AC and features a 3-pole configuration.
The breaker has a nominal current rating of 200A at 40°C, with a derated current of 189A at 50°C. Its breaking capacity is rated at 65kA at 480V, 100kA at 240V, and 25kA at 600V, ensuring reliable performance under fault conditions. The overcurrent release is of type TM210 with LI protection functionality.
Designed for convenience, it supports DIN rail mounting and front connections using a nut keeper kit. The mechanical service life is typically 20,000 switching cycles, with electrical endurance varying based on voltage and load conditions. This circuit breaker is also designated as HACR Type.
Key technical data includes a maximum power loss of 43W and an active power loss of 14.17W per pole. The dimensions are 185mm in height, 105mm in width, and 83mm in depth. It is marked according to UL 489 and has a switching capacity class of H according to IEC 60947.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage for this circuit breaker is 690 V AC.
The operational current rating is 200A at 40°C, and it is 189A at 50°C.
The breaking capacity is 65kA at 480V, 100kA at 240V, and 25kA at 600V.
This circuit breaker has 3 poles.
This circuit breaker supports DIN rail mounting.
Yes, the RoHS status is RoHS3 Compliant.
The Moisture Sensitivity Level (MSL) is 1 Unlimited.