| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
The Siemens 3VA5220-5ED61-0AA0 is a 2-pole molded-case circuit breaker from the SENTRON 3VA5 series, designed for system protection applications. It has a maximum rated operational current of 250A and a permanent rated current (Iu) of 200A, with derated values at higher temperatures.
This circuit breaker operates at a maximum rated insulation voltage (Ui) of 800V and a maximum rated operational voltage (Ue) of 690V AC at 50/60Hz, and 500V DC. It offers a breaking capacity (Icu) of 55 kA at 415V and 35 kA at 480V according to UL 489 standards.
The device features a TM210 overcurrent release with LI protection function. It has a mechanical service life of typically 20,000 switching cycles and an electrical endurance of 8,000 cycles at 380/415V AC. The dimensions are 7.3 inches (185 mm) in height, 4.1 inches (105 mm) in width, and 3.3 inches (83 mm) in depth. Mounting is designed for DIN rail.
Compliance includes UL 489, CE, CSA, EAC, VDE, and CCC approvals. It is rated RoHS3 Compliant, MSL 1, and REACH Unaffected.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage (Ue) for this circuit breaker is 690 V AC at 50/60Hz and 500 V DC.
The breaking capacity according to UL 489 at 480V is 35 kA.
This circuit breaker supports DIN Rail mounting.
The permanent rated current (Iu) is 200 A.
The dimensions are 7.3 inches (185 mm) in height, 4.1 inches (105 mm) in width, and 3.3 inches (83 mm) in depth.