| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Connection Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage | |
| Voltage Rating | |
| Width |
The Siemens 3VA5220-0MU32-0AA0 is a 3-pole molded-case circuit breaker designed for starter protection. It operates at a rated voltage of 690V AC and has an operational current rating of 200A across various temperature ranges from 40°C to 70°C.
This circuit breaker offers a maximum short-circuit breaking capacity (Icu) of 100 kA at 240 V, 70 kA at 415 V, and 10 kA at 690 V. The operating short-circuit current capacity (Ics) is also 100 kA at 240 V. Its short-circuit current making capacity (Icm) reaches 220 kA at 240 V.
With a mechanical service life of typically 20,000 switching cycles, the 3VA5220-0MU32-0AA0 is built for durability. It features a front connection with nut keeper kits on both ends for main current circuit connections. The dimensions are 185 mm in height, 105 mm in width, and 83 mm in depth. It is designed for DIN rail mounting.
This model is HACR Type compliant and uses the TM120M overcurrent release. It does not include communication functions, phase failure detection, or other measurement functions. The ground-fault monitoring version is without.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operating voltage for this circuit breaker at AC rated value is 690 V.
The maximum breaking capacity (Icu) is 100 kA at 240 V, 70 kA at 415 V, and 10 kA at 690 V.
The operational current at 40°C is 200 A.
The dimensions are 185 mm in height, 105 mm in width, and 83 mm in depth.
Yes, it is RoHS3 Compliant.
The Moisture Sensitivity Level is 1 Unlimited.