This Siemens 3VA5215-6GC41-0AA0 is a 4-pole molded-case circuit breaker from the 3VA5 series, designed for system protection applications. It has a maximum rated operational current of 250A and a continuous current rating (Iu) of 150A, with operational current varying slightly with temperature.
The circuit breaker offers a breaking capacity of 65kA at 480V and 100kA at 240V according to UL 489 standards. It is equipped with a TM230 overcurrent release with LI protection function. The N-conductor protection is rated at 100%.
With a rated insulation voltage (Ui) of 800V and a maximum rated operational voltage (Ue) of 690V AC, this breaker is suitable for various industrial applications. It features a mechanical service life of 20,000 cycles and electrical endurance ratings of up to 8,000 cycles at 380/415V.
The unit is designed for DIN rail mounting and has a HACR Type designation, indicating its suitability for Heating, Air Conditioning, and Refrigeration circuits. It is UL489 listed, along with other approvals from CE, CSA, EAC, and CCC.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The continuous current rating (Iu) is 150A, and the maximum rated operational current of the frame size is 250A.
The breaking capacity according to UL 489 is 65kA at 480V.
This circuit breaker has 4 poles.
The maximum rated operational voltage (Ue) with AC 50/60Hz is 690V.
The mounting type is DIN Rail.