| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
This Siemens 3VA5215-6ED36-2AA0 is a 3-pole circuit breaker designed for line protection. It operates with a rated insulation voltage of 800V and a rated operating voltage of up to 690V AC or 750V DC.
The breaker features a current rating of 150A at 40°C, with derated values at higher temperatures. Its overcurrent release is type TM210 with LI protection functions. The switching capacity according to IEC 60947 includes an Icu of 70 kA at 415V and an Ics of 70 kA at 415V. Under UL 489 standards, it provides a current breaking capacity of 65 kA at 480V.
Adjustable parameters include Ir from 150A to 150A and Ii from 1500A to 1500A. The device has a mechanical service life of 20,000 operating cycles and electrical endurance ratings varying by voltage and load conditions.
It is designed for DIN rail mounting and features a lever actuator. The breaker is marked as 100%-rated according to UL 489 and is suitable for HACR type applications.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage for this circuit breaker is 690 V at AC and 750 V at DC.
The operational current is 150 A at 40 °C.
The maximum short-circuit current breaking capacity (Icu) is 70 kA at 415 V according to IEC 60947, and the current breaking capacity is 65 kA at 480 V according to UL 489.