| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage | |
| Voltage Rating | |
| Width |
This Siemens 3VA5 series molded-case circuit breaker, part number 3VA5215-6EC36-1AA0, is engineered for system protection applications. It features a 3-pole configuration and a rated operational current of 150A at 40°C, with derated values at higher temperatures.
The circuit breaker provides a breaking capacity of 65kA at 480V and 100kA at 240V, according to UL 489 standards. It is equipped with a TM230 overcurrent release with LI protection function. The device operates at a rated voltage of 690V AC.
Designed for DIN rail mounting, this breaker has a mechanical service life of typically 20,000 switching cycles. Its dimensions are 185mm in height, 105mm in width, and 83mm in depth. The breaker is also designated as HACR Type according to UL 489.
Key electrical specifications include a maximum power loss of 30W and an active power loss of 9.7W per pole at rated current in hot operating state. The electrical endurance varies with voltage, with 8,000 cycles at 380/415V and 480V, and 4,000 cycles at 690V.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage is 690 V AC.
The breaking capacity at 480V is 65 kA.
The operational current rating at 40°C is 150 A.
It uses the TM230 overcurrent release with LI protection function.
The mounting type is DIN Rail.