| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating | |
| Width |
The Siemens 3VA5212-6EC31-1AA0 is a 3-pole molded-case circuit breaker designed for system protection applications. It has a rated operational current of 125A and offers a breaking capacity of 65kA at 480V, with a maximum frame size current of 250A.
This circuit breaker utilizes the TM230 overcurrent release with LI protection function. It is built to UL 489 standards and is designated as an HACR Type breaker. The device operates within an ambient temperature range of -25°C to 70°C and has a mechanical service life of 20,000 switching cycles.
With a height of 185mm, width of 105mm, and depth of 83mm, the 3VA5212-6EC31-1AA0 is designed for DIN rail mounting. It features a maximum power loss of 22.6W and an active power loss of 7.53W per pole under rated conditions. The breaker has an IP40 protection class on the front.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 125A at temperatures up to 50°C, with reduced ratings at higher temperatures.
The breaking capacity is 65kA at 480V and 25kA at 600V.
This circuit breaker has 3 poles.
The operating ambient temperature range is from -25°C to 70°C.
The mounting type is DIN Rail.