This Siemens 3VA5212-5ED36-0AA0 is a molded-case circuit breaker from the 3VA5 series, designed for system protection applications. It features a 3-pole configuration and a rated operational current of 125A at 40°C, with derated values at higher temperatures.
The circuit breaker operates at a rated voltage of 690V AC and has a maximum breaking capacity of 35kA at 480V according to UL 489 standards. It also meets IEC 60947 standards with a breaking capacity of 55kA at 415V.
With a mechanical service life of 20,000 cycles and electrical endurance ratings of up to 8,000 cycles, this breaker is built for durability. It is suitable for HACR Type applications and mounts via DIN rail.
Key electrical specifications include a rated insulation voltage of 800V and a maximum power loss of 23W. The dimensions are 185mm in height, 105mm in width, and 83mm in depth.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operational voltage for this circuit breaker is 690 V AC.
The operational current is 125 A at 40°C.
The breaking capacity according to UL 489 is 35 kA at 480 V.
The RoHS status is RoHS3 Compliant.
The Moisture Sensitivity Level is 1 Unlimited.