This Siemens 3VA5210-5EF32-0AA0 is a molded-case circuit breaker from the 3VA5 series, designed for system protection applications. It features a 3-pole configuration and a rated operational current of 100A at 40°C, with derated values at higher temperatures.
The circuit breaker operates at a rated voltage of 690V AC and has a maximum insulation voltage of 800V. It provides a breaking capacity of 35kA at 480V according to UL 489 standards, and 55kA at 415V according to IEC 60947.
With a mechanical service life of 20,000 switching cycles, this breaker is built for durability. Its dimensions are 185mm in height, 105mm in width, and 83mm in depth. The mounting type is DIN rail.
Key electrical protection functions include overload protection (Ir=80A...100A) and short-circuit protection (Ii=5...10 x In). It is also designed as a Heating, Air Conditioning, and Refrigeration (HACR Type) circuit breaker.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current is 100A at 40°C, derating to 84A at 70°C.
The rated operating voltage at AC is 690V, with a maximum rated operational voltage of 750V DC and a rated insulation voltage of 800V.
According to UL 489, the breaking capacity is 35kA at 480V. According to IEC 60947, it is 55kA at 415V and 7kA at 690V.
This circuit breaker is designed for DIN rail mounting.
The dimensions are 185 mm in height, 105 mm in width, and 83 mm in depth.
The overcurrent release offers LI protection.