| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
This Siemens 3VA5 series molded-case circuit breaker, part number 3VA5195-6EF36-0AA0, is engineered for robust system protection. It features a 3-pole configuration and a nominal current rating of 15A, with an operational current that varies slightly with temperature, down to 14A at 50°C and above.
The breaker provides a high breaking capacity, rated at 65kA at 480V according to UL 489 standards, and 70kA at 415V according to IEC 60947. Its insulation voltage is rated at 800V, with a maximum operational voltage of 690V AC. The overcurrent release is of type TM240 with LI protection, allowing for adjustable overload protection from 12A to 15A (Ir) and short-circuit protection from 10 to 20 times the rated current (Ii).
Designed for DIN rail mounting, this circuit breaker has a mechanical service life of typically 20,000 switching cycles. It meets various approval standards including CCC, CE, UL489, and VDE. The breaker is also designated as HACR, HID, and SWD type according to UL 489.
Key electrical specifications include a maximum power loss of 10.6W and an active power loss per pole of 3.53W under hot operating conditions. The electrical endurance is rated at 8,000 cycles at 380/415V AC-1 and 4,000 cycles at 690V AC-1.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operational voltage at AC is 690 V.
The breaking capacity according to UL 489 at 480 V is 65 kA.
The nominal current rating is 15A.
This circuit breaker has 3 poles.
The mounting type is DIN Rail.