This Siemens 3VA5 series molded-case circuit breaker, part number 3VA5195-6EF32-0AA0, is designed for system protection. It features a 3-pole configuration with a rated operational current of 15A at 40°C, derating to 14A at higher temperatures up to 70°C.
The breaker operates at a rated voltage of 690V AC and has a significant breaking capacity, rated at 65kA at 480V according to UL 489 standards, and up to 150kA at 240V according to IEC 60947 standards. The overcurrent release is a TM240 type with LI protection function, and the response current is adjustable from 11A to 15A.
With a mechanical service life of 20,000 switching cycles, this circuit breaker is built for durability. Its dimensions are 140mm in height, 76.2mm in width, and 76.5mm in depth. It is designed for DIN rail mounting.
This model is also recognized as HACR, HID, and SWD type according to UL 489, making it suitable for various applications including HVAC and high-intensity discharge lighting circuits.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 15A at 40°C, and it derates to 14A at temperatures from 50°C to 70°C.
The rated operational voltage at AC is 690 V.
The breaking capacity according to UL 489 is 65 kA at 480 V.
This circuit breaker is designed for DIN rail mounting.
It features TM240 overcurrent release with LI protection function.
Yes, it is designed as a Heating, Air Conditioning, and Refrigeration (HACR) Type circuit breaker according to UL 489.