The Siemens 3VA5195-6ED22-1AA0 is a 2-pole molded-case circuit breaker from the 3VA5 series, designed for system protection applications. It operates at a rated voltage of 415V AC and has an operational current of 15A at 40°C, derating to 14A at higher temperatures up to 70°C.
This circuit breaker offers a significant breaking capacity of 65kA at 480V and 150kA at 240V, ensuring reliable protection against overcurrents. The overcurrent release is of type TM210 with LI protection function. It is designed for front connection with nut keeper kits on both ends.
Key electrical endurance figures include 8,000 switching cycles at AC-1 for 380/415V and 480V, and 4,000 cycles at 690V and 600V. The mechanical service life is typically 20,000 cycles. The unit has a maximum power loss of 6.5W, with 3.25W active power loss per pole under rated conditions.
With a width of 50.8mm and depth of 76.5mm, it is suitable for DIN rail mounting. The circuit breaker is UL489 listed and meets HACR, HID, and SWD type requirements. It is also marked as RoHS3 Compliant and MSL 1.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage for this circuit breaker is 415 V AC.
The operational current is 15A at 40°C, derating to 14A at 50°C and above.
The breaking capacity is 65 kA at 480 V and 150 kA at 240 V.
This circuit breaker has 2 poles.
This component is RoHS3 Compliant.
The Moisture Sensitivity Level is 1.