| Voltage Rating |
This Siemens 3VA5195-6ED16-0AA0 is a 1-pole molded-case circuit breaker designed for system protection. It belongs to the SENTRON series and operates with a rated current of 15A. The circuit breaker offers a breaking capacity of 50kA at 277V according to UL 489 standards and 5kA at 415V according to IEC 60947.
Key electrical specifications include an insulation voltage of 500V, a maximum operational voltage of 125V DC, and an operating voltage of 415V AC. The overcurrent release is of type TM210 with LI protection function. It is designed for HACR, HID, and SWD type applications under UL 489.
The device has a typical mechanical service life of 20,000 switching cycles and an electrical endurance of 8,000 cycles at 380/415V AC. It mounts on a DIN rail and has a net weight of 0.401 kg. The power loss is a maximum of 3.2W.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operating voltage is 415 V AC.
The operational current is 15 A at 40°C and 45°C.
The breaking capacity is 50 kA at 277 V.
The RoHS status is RoHS3 Compliant.
The MSL is 1 Unlimited.