| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Connection Type | |
| Current Rating (Amps) | |
| Dimensions | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Temperature Rating | |
| Trip Range | |
| Voltage Rating |
This Siemens 3VA5180-6ED26-0AA0 is a 2-pole molded-case circuit breaker designed for system protection. It features an 80A operational current at 40°C, with derated values at higher temperatures. The breaker offers a breaking capacity of 65kA at 480V according to UL 489 standards and 70kA at 415V according to IEC 60947.
The overcurrent release is a TM210 type with LI protection function. It has a fixed short-circuit protection setting of 10 x In. The insulation voltage is rated at 600V, with a maximum operational voltage of 250V DC and 415V AC.
Designed for DIN rail mounting, this circuit breaker has a compact design and an IP40 enclosure. It is suitable for HACR type applications. The mechanical service life is typically 20,000 switching cycles, with electrical endurance varying based on voltage and load conditions.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current is 80A at 40°C, derating to 72A at 70°C.
The breaking capacity is 65kA at 480V (UL) and 70kA at 415V (IEC).
It features a TM210 overcurrent release with LI protection function and a fixed short-circuit protection setting of 10 x In.
The insulation voltage is rated at 600V, with a maximum operational voltage of 250V DC and 415V AC.
Yes, it is RoHS3 Compliant.
It is designed for DIN Rail mounting.