| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
This Siemens 3VA5 series molded-case circuit breaker, part number 3VA5180-6EC36-0AA0, is a 3-pole unit designed for system protection. It features an 80A operational current at 40°C and a breaking capacity of 65kA at 480V according to UL 489 standards. The circuit breaker utilizes a TM230 overcurrent release with LI protection function, offering adjustable short-circuit protection from 5 to 10 times the rated current.
With a rated operational voltage of 690V AC and an insulation voltage of 800V, this breaker is suitable for various industrial applications. It boasts a mechanical service life of 20,000 switching cycles and electrical endurance ratings of up to 8,000 cycles at 480V. The unit is HACR Type approved and mounts via DIN rail.
Key electrical specifications include a maximum power loss of 19.3W and an active power loss per pole of 6.43W at AC in hot operating state. The breaking capacity according to IEC 60947 standards is 150kA at 240V, 70kA at 415V, and 10kA at 690V. The short-circuit making capacity (Icm) is 330kA at 240V, 154kA at 415V, and 17kA at 690V.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 80A at 40°C.
The breaking capacity at 480V is 65kA according to UL 489.
The rated operating voltage is 690V AC.
This circuit breaker has 3 poles.
It supports DIN Rail mounting.
The protection function is LI.