| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Overload Protection | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
This Siemens 3VA5180-5ED41-0AA0 is a 4-pole molded-case circuit breaker designed for system protection. It operates with a rated current of 80A and a maximum operational voltage of 690V AC or 600V DC. The circuit breaker offers a breaking capacity of 35kA at 480V, 55kA at 415V, and 7kA at 690V according to IEC standards.
Key electrical features include overload protection set at Ir=80A and fixed short-circuit protection at Ii=10 x In. The device is built with a TM210 overcurrent release and provides LI protection functions. It is suitable for HACR Type applications as per UL 489 standards.
The breaker has a mechanical service life of typically 15,000 switching cycles and electrical endurance ratings of 8,000 cycles at 380/415V and 4,000 cycles at 690V. It is designed for DIN rail mounting.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage is 690V AC.
The rated operational current is 80A at 40°C.
The breaking capacity at 480V is 35kA.
It mounts on a DIN rail.
It complies with CCC, CE, CSA, EAC, UL489, and VDE standards.