This Siemens 3VA5180-5ED32-0AA0 is a 3-pole molded-case circuit breaker from the 3VA5 series, designed for system protection applications. It features an operational current rating of 80A at 40°C, with a derated current of 72A at 70°C. The breaker operates at a rated voltage of 690V AC and has a maximum insulation voltage (Ui) of 800V.
With a breaking capacity of 35kA at 480V according to UL 489 standards, and 55kA at 415V according to IEC 60947, this circuit breaker provides robust protection. It utilizes the TM210 overcurrent release with LI protection function. The mechanical service life is rated for 20,000 switching cycles, and electrical endurance varies by voltage, with 8,000 cycles at 380/415V and 4,000 cycles at 690V.
The unit is designed for DIN rail mounting and has dimensions of 140mm height, 76.2mm width, and 76.5mm depth. It does not feature communication or other measurement functions. The breaker is compliant with RoHS3, REACH Unaffected, and has an MSL of 1.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current is 80A at 40°C, derating to 72A at 70°C.
The breaking capacity is 35kA at 480V according to UL 489, and 55kA at 415V according to IEC 60947.
The rated operating voltage is 690V AC.
This circuit breaker has 3 poles.
It is designed for DIN rail mounting.