| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Overload Protection | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
The Siemens 3VA5180-5ED26-1AA0 is a 2-pole molded-case circuit breaker designed for system protection. It features an operational current rating of 80A at 40°C, with derated values at higher temperatures. The breaker provides a breaking capacity of 35kA at 480V and 18kA at 600Y/347V, conforming to UL489 standards.
This circuit breaker utilizes TM210 overcurrent release with LI protection function. It has a rated AC voltage of 415V and a maximum power loss of 12.86W. The mechanical service life is typically 20,000 switching cycles, with electrical endurance varying based on voltage and load conditions.
Designed for DIN rail mounting, the 3VA5180-5ED26-1AA0 is suitable for applications requiring reliable circuit protection. It is HACR Type compliant. The unit weighs 0.668 kg.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 80A at 40°C, decreasing to 72A at 70°C.
The breaking capacity according to UL 489 at 480V is 35kA.
This circuit breaker has 2 poles.
The rated AC voltage is 415V.
The typical mechanical service life is 20,000 switching cycles.
The RoHS status is RoHS3 Compliant.
The Moisture Sensitivity Level is 1 Unlimited.