3VA5180-1MH32-0AA0 The Siemens 3VA5180-1MH32-0AA0 is a 3-pole molded-case circuit breaker designed for starter protection. It offers an 80A operational current and a 690V operating voltage.
Mfr Part #:

3VA5180-1MH32-0AA0

Mfr Name: Siemens
Siemens
The Siemens 3VA5180-1MH32-0AA0 is a 3-pole molded-case circuit breaker designed for starter protection. It offers an 80A operational current and a 690V operating voltage.
Stock on Request
$ Price Range: $0.99

3VA5180-1MH32-0AA0 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Current Rating (Amps)
Depth
Height
Illumination
Mounting Type
Number of Poles
Storage Temperature
Tape & Reel
Voltage
Voltage Rating
Width

3VA5180-1MH32-0AA0 Description

Short technical summary and product information.

The Siemens SENTRON 3VA5180-1MH32-0AA0 is a 3-pole molded-case circuit breaker designed for starter protection applications. It operates at a rated voltage of 690V AC and has an operational current of 80A across a temperature range of 40°C to 70°C.

 

This circuit breaker features a high breaking capacity, with a maximum short-circuit current (Icu) of 150 kA at 240V and 70 kA at 415V. The operating short-circuit current (Ics) is also 150 kA at 240V and 70 kA at 415V. Its short-circuit making capacity (Icm) is 330 kA at 240V and 154 kA at 415V.

 

With a mechanical service life of typically 20,000 switching cycles and electrical endurance ratings of up to 8,000 cycles at 380/415V, this breaker is built for durability. It is HACR Type certified according to UL 489. The unit has a net weight of 1.022 kg and dimensions of 140mm height, 76.2mm width, and 76.5mm depth. It is designed for front connection with nut keeper kits on both ends.

3VA5180-1MH32-0AA0 Quick Information

Product Type: Molded-case circuit breaker
Series: SENTRON
Canonical Name: Siemens SENTRON Molded-case circuit breaker, Starter protection, 3-pole, 80A operational current
Subcategory: Starter protection

3VA5180-1MH32-0AA0 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3VA5180-1MH32-0AA0 Estimated Pricing

Qty Low High
1+ $0.99 $0.99

Estimated market price range - modelled values for guidance only, not live distributor offers.

3VA5180-1MH32-0AA0 Features

  • 3-pole molded-case circuit breaker
  • 80A operational current rating
  • 690V AC operating voltage
  • 150kA breaking capacity at 240V
  • HACR Type certified

3VA5180-1MH32-0AA0 Applications

  • Suitable for starter protection
  • Designed for HACR Type applications
  • Industrial control panels
  • Power distribution systems

3VA5180-1MH32-0AA0 FAQs

5 frequently asked questions generated from this part’s specifications.
What is the operating voltage for this circuit breaker?

The operating voltage is 690 V at AC rated value.

What is the maximum operational current at 40°C?

The operational current at 40°C is 80 A.

What is the maximum short-circuit breaking capacity at 240V?

The maximum short-circuit breaking capacity (Icu) at 240V is 150 kA.

What are the dimensions of this circuit breaker?

The dimensions are 140 mm height, 76.2 mm width, and 76.5 mm depth.

Is this circuit breaker HACR Type certified?

Yes, it is HACR Type certified according to UL 489.

Home