| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Overload Protection | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating | |
| Width |
The Siemens 3VA5160-6ED31-0AA0 is a 3-pole molded-case circuit breaker from the 3VA series, designed for system protection applications. It features a rated operational current of 60A at 40°C and a maximum rated operational voltage of 690V AC.
This circuit breaker provides a breaking capacity of 65kA at 480V according to UL 489 standards, and 70kA at 415V according to IEC 60947 standards. The overcurrent release is of type TM210 with LI protection function. It has a maximum power loss of 13.6W and a mechanical service life of typically 15,000 switching cycles.
Designed for DIN rail mounting, the 3VA5160-6ED31-0AA0 has dimensions of 140mm in height, 76.2mm in width, and 76.5mm in depth. It is HACR Type rated and compliant with various approval agencies including CCC, CE, CSA, EAC, UL489, and VDE.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The continuous current rating (Iu) is 60A at 40°C.
The maximum rated operational voltage is 690V AC at 50/60Hz and 500V DC.
The breaking capacity is 65kA at 480V (UL 489) and 70kA at 415V (IEC 60947).
It is designed for DIN rail mounting.
It features TM210 overcurrent release with LI protection function.