| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Overload Protection | |
| Voltage Rating |
This Siemens 3VA5160-6ED26-1AA0 is a 2-pole molded-case circuit breaker from the 3VA5 series, designed for system protection. It features a nominal current rating of 60A at 40°C, with operational current decreasing at higher temperatures. The circuit breaker offers a significant breaking capacity of 65kA at 480V and 150kA at 240V, with a switching capacity class of H according to IEC 60947.
Equipped with TM210 overcurrent release and LI protection function, this breaker is suitable for HACR type applications according to UL 489. It has a mechanical service life of 20,000 switching cycles and electrical endurance ratings of up to 8,000 cycles at 380/415V.
The unit is designed for DIN rail mounting and has a net weight of 0.668 kg. It operates with a rated AC voltage of 415V and has a maximum power loss of 10.26W.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 60A at 40°C, decreasing to 54A at 70°C.
The breaking capacity is 65kA at 480V and 150kA at 240V.
This circuit breaker has 2 poles.
It supports DIN rail mounting.
The rated AC operating voltage is 415V.
The overcurrent release type is TM210 with LI protection function.