This Siemens 3VA5160-5ED21-0AA0 is a 2-pole molded-case circuit breaker from the SENTRON series, designed for system protection applications. It has a rated operational current of 60A at 40°C and a maximum frame size current of 125A.
The circuit breaker offers a breaking capacity of 35kA at 480V according to UL 489 standards and 55kA at 415V according to IEC 60947 standards. It operates with a rated insulation voltage of 600V and a maximum rated operational voltage of 415V AC or 250V DC.
Key electrical features include TM210 overcurrent release with LI protection function. The device has a mechanical service life of 15,000 switching cycles and electrical endurance ratings of 8,000 cycles at 380/415V AC and 4,000 cycles at 690V AC.
Mechanically, the unit has dimensions of 140mm height, 50.8mm width, and 76.5mm depth. It is designed for DIN rail mounting.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The continuous current rating (Iu) is 60A at 40°C, with derated values at higher temperatures.
The breaking capacity is 35kA at 480V per UL 489 and 55kA at 415V per IEC 60947.
The maximum rated operational voltage is 415V AC at 50/60Hz and 250V DC.
This circuit breaker has 2 poles.
The circuit breaker supports DIN rail mounting.