| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating | |
| Width |
This Siemens 3VA5160-5EC31-0AA0 is a molded-case circuit breaker designed for system protection. It features a 3-pole configuration and a rated operational current of 60A at 40°C, with a maximum frame size current of 125A.
The circuit breaker offers a maximum rated operational voltage of 690V AC and 500V DC. Its breaking capacity according to UL standards is 35kA at 480V and 18kA at 600Y/347V. According to IEC standards, the breaking capacity is 55kA at 415V and 7kA at 690V. The overcurrent release type is TM230 with LI protection function.
With a mechanical service life of typically 15,000 switching cycles, this breaker is built for durability. It is designed for DIN rail mounting and has dimensions of 140mm height, 76.2mm width, and 76mm depth. The device includes adjustable response current settings for I_g from 42A to 60A and for I_i from 300A to 600A.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage for this circuit breaker is 690 V with AC 50/60Hz and 500 V with DC.
The breaking capacity according to UL 489 is 35 kA at 480 V.
The permanent rated current (Iu) is 60 A.
The dimensions are 140 mm in height, 76.2 mm in width, and 76 mm in depth.
This circuit breaker supports DIN Rail mounting.