This Siemens 3VA5160-4ED21-0AA0 is a 2-pole molded-case circuit breaker from the SENTRON series, designed for system protection. It offers a rated operational current of 60A at 40°C and a breaking capacity of 25kA at 480V according to UL 489 standards. The circuit breaker utilizes a TM210 overcurrent release with LI protection function.
With a rated insulation voltage of 600V and a maximum rated operational voltage of 415V AC, this device is suitable for various applications. It has a mechanical service life of 15,000 switching cycles and electrical endurance ratings of 8,000 cycles at 380/415V AC and 4,000 cycles at 690V AC. The dimensions are 140mm in height, 50.8mm in width, and 76.5mm in depth.
The breaker is designed for HACR type applications and mounts on a DIN rail. It features fixed short-circuit protection set at 10 x In and overload protection set at Ir=60A. The switching capacity according to IEC 60947 is class S, with a maximum short-circuit current of 36kA at 415V.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated insulation voltage is 600 V.
The maximum rated operational voltage with AC 50/60Hz is 415 V.
The maximum rated operational voltage with DC is 250 V.
The mechanical service life is 15,000 switching cycles.
The breaking capacity current at 240 V is 65 kA.
The current rating is 60 A.