| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating | |
| Width |
This Siemens 3VA5 series molded-case circuit breaker, part number 3VA5150-6EC32-0AA0, is engineered for robust system protection. It operates with a 3-pole configuration and offers a nominal operational current of 50A at 40°C, with derated values at higher temperatures.
The breaker boasts a high breaking capacity, rated at 65kA at 480V according to UL 489 standards, and 150kA at 240V. It also meets IEC 60947 standards with a breaking capacity of 70kA at 415V.
Key electrical specifications include a rated insulation voltage of 800V and a maximum operational voltage of 500V DC. The overcurrent release is of type TM230 with LI protection function, featuring adjustable short-circuit protection from 5 to 10 times the rated current.
Mechanically, the unit has a typical service life of 20,000 cycles and is designed for DIN rail mounting. Its dimensions are 140mm in height, 76.2mm in width, and 76.5mm in depth, with a net weight of 1.034 kg.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current is 50A at 40°C, derating to 44A at 70°C.
The breaking capacity is 65kA at 480V according to UL 489, and 150kA at 240V according to IEC 60947.
The rated insulation voltage (Ui) is 800V.
This circuit breaker has 3 poles.
It is designed for DIN rail mounting.