This Siemens 3VA5140-6ED26-0AA0 is a 2-pole molded-case circuit breaker from the 3VA51 UL frame series, designed for system protection. It offers a rated operational voltage of 415V AC and a maximum operational voltage of 250V DC.
The circuit breaker has a current rating of 40A at 40°C, with derated values at higher temperatures. It features a TM210 overcurrent release with LI protection function, providing overload protection with a fixed setting of Ir=40A and fixed short-circuit protection of Ii=10 x In. The breaking capacity according to UL 489 is 65kA at 480V.
With a mechanical service life of 20,000 cycles and electrical endurance ratings of 8,000 cycles at 380/415V AC-1, this breaker is built for durability. It is HACR Type certified, suitable for Heating, Air Conditioning, and Refrigeration applications. The device has a maximum power loss of 7.46W and a net weight of 0.657 kg.
Mounting is via DIN rail, and the device construction is fixed built-in technique. It has an IP40 degree of protection. The breaker is not equipped with integrated earth fault protection, motor drive, or communication functions.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operational voltage for this circuit breaker is 415 V AC.
The operational current rating at 40°C is 40 A.
The breaking capacity according to UL 489 is 65 kA at 480 V.
This breaker has a TM210 overcurrent release with LI protection function.
Yes, this circuit breaker is designed as HACR Type.
The mounting type is DIN Rail.