| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
This Siemens 3VA5140-6ED16-0AA0 is a 1-pole molded-case circuit breaker from the SENTRON series, designed for system protection applications. It operates at a rated AC voltage of 415V and has a maximum DC operational voltage of 125V.
The circuit breaker offers an operational current of 40A at 40°C, with a fixed short-circuit protection setting (Ii) of 10 x In. Its breaking capacity according to IEC 60947 is class H, with a maximum short-circuit current (Icu) of 55 kA at 240V and 5 kA at 415V. Under UL 489 standards, it provides a breaking capacity of 50 kA at 277V.
With a mechanical service life of typically 20,000 switching cycles and electrical endurance of 8,000 cycles at 380/415V AC-1, this breaker is built for durability. It features TM210 overcurrent release with LI protection function and is suitable for HACR Type applications as per UL 489.
The unit is designed for DIN rail mounting and has a net weight of 0.401 kg. It is RoHS3 compliant, has an MSL of 1, and is REACH unaffected.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current is 40A.
The breaking capacity at 415V is 5kA.
It uses DIN rail mounting.
The insulation voltage is 500V.
No, it does not include ground-fault monitoring.