This Siemens 3VA5140-5ED26-0AA0 is a 2-pole molded-case circuit breaker from the 3VA51 series, designed for system protection applications. It features a current rating of 40A and a breaking capacity of 35kA at 480V, with an operating voltage of 415V AC.
The circuit breaker utilizes a TM210 overcurrent release with LI protection function. It has a mechanical service life of 20,000 cycles and electrical endurance ratings suitable for various AC voltage levels. The device is suitable for HACR Type applications according to UL 489.
Mounting is designed for DIN rail installation. The breaker has a maximum power loss of 7.46W and an active power loss per pole of 3.73W in hot operating state. It is compliant with RoHS3 standards and has an MSL of 1.
Key specifications include an insulation voltage of 600V and a maximum rated operational voltage of 250V DC. The breaking capacity according to IEC 60947 is class M, with Icu at 415V being 55kA and Ics at 415V also being 55kA. The short-circuit making capacity (Icm) at 415V is 121kA.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operating voltage is 415 V AC.
It has 2 poles.
The insulation voltage is rated at 600 V.
It is approved by CCC, CE, UL489, and VDE.
The mechanical service life is 20,000 cycles.