| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating | |
| Width |
This Siemens 3VA5135-6ED36-0AA0 is a molded-case circuit breaker designed for system protection. It operates with a rated insulation voltage of 800V and a maximum operational voltage of 500V DC, with a rated AC operating voltage of 690V.
The breaker features a TM210 overcurrent release with LI protection function and a fixed short-circuit protection setting of 10 x In. It has a 35A operational current at 40°C, with derated values at higher temperatures. The switching capacity according to IEC 60947 is class H, with a maximum breaking capacity (Icu) of 150kA at 240V and 65kA at 480V according to UL 489.
Designed for DIN rail mounting, this circuit breaker has mechanical dimensions of 76.2mm width, 76.5mm depth, and 140mm height. It has a typical mechanical service life of 20,000 switching cycles and electrical endurance ratings suitable for various AC voltage levels.
Compliance includes UL 489 HACR and HID type designations. It is RoHS3 compliant, has an MSL of 1, and is REACH unaffected.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage for this circuit breaker at AC is 690 V.
The operational current at 40°C is 35 A.
The breaking capacity according to UL 489 at 480 V is 65 kA.
This circuit breaker is designed for DIN Rail mounting.
This component is RoHS3 Compliant.
The Moisture Sensitivity Level (MSL) is 1 Unlimited.