This Siemens 3VA5 molded-case circuit breaker, part number 3VA5135-6ED30-0DD0, is a 3-pole unit designed for line protection. It features a rated operational current of 35A at 40°C, with a maximum operating voltage of 690V AC. The breaker provides a breaking capacity of 65kA at 480V according to UL 489 standards and 150kA at 240V according to IEC 60947.
With a TM210 overcurrent release and LI protection function, it offers overload protection with Ir=35A and fixed short-circuit protection at Ii=10 x In. The mechanical service life is rated at a typical 20,000 switching cycles, with electrical endurance varying by voltage and load conditions.
The unit has a compact design with dimensions of 76.2mm width, 76.5mm depth, and 140mm height, suitable for DIN rail mounting. It is also listed as HACR and HID Type according to UL 489.
General technical data includes a rated insulation voltage of 800V and a maximum power loss of 13.9W. The breaker is suitable for system protection applications.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current is 35A at 40°C, decreasing to 32A at 70°C.
The maximum operating voltage at AC is 690 V.
The breaking capacity according to UL 489 is 65 kA at 480 V.
This circuit breaker has 3 poles.
It supports DIN Rail mounting.