| Voltage Rating |
This Siemens 3VA5135-5EC41-0AA0 is a 4-pole molded-case circuit breaker from the 3VA5 series, designed for system protection. It has a permanent rated current (Iu) of 35A and a maximum rated operational voltage of 690V AC (50/60Hz) or 600V DC. The breaker offers a breaking capacity of up to 85 kA at 240V AC according to UL 489 standards and 55 kA at 415V AC according to IEC 60947.
Key electrical features include adjustable overcurrent response values with a minimum of 35A and a minimum short-circuit response value of 175A, up to a maximum of 350A. The breaker has a mechanical service life of typically 15,000 switching cycles and electrical endurance ratings of up to 8,000 cycles at 380/415V AC.
Designed for DIN rail mounting, this circuit breaker has a height of 5.5 inches. It operates with a lever actuator type and is suitable for HACR Type applications. The breaker has a maximum power loss of 11W.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage for this circuit breaker is 690 V with AC 50/60Hz and 600 V with DC.
The permanent rated current (Iu) is 35 A, and the operational current at 40°C is also 35 A.
According to IEC 60947, the breaking capacity is 55 kA at 415 V. According to UL 489, the breaking capacity is 35 kA at 480 V.
This circuit breaker is designed for DIN rail mounting.
This component is RoHS3 Compliant.
The Moisture Sensitivity Level (MSL) is 1 Unlimited.