| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
The Siemens 3VA5135-4ED31-0AA0 is a 3-pole molded-case circuit breaker designed for system protection. It features a current rating of 35A and a maximum operational voltage of 690V AC or 500V DC. The breaker provides a breaking capacity of 25kA at 480V according to UL standards, and 55kA at 240V according to IEC standards.
With a frame size of 125A, this circuit breaker is suitable for various applications. It has a mechanical service life of 15,000 switching cycles and electrical endurance ratings that vary with voltage and load conditions. The unit is designed for DIN rail mounting and has physical dimensions of 5.5 inches in height, 3 inches in width, and 3 inches in depth.
Key electrical protection functions include overload and short-circuit protection with an adjustable response current (Ir) of 35A and an adjustable short-circuit response (Ii) from 350A to 350A. The overcurrent release type is TM210 with LI protection function.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage for this circuit breaker is 690 V AC at 50/60 Hz and 500 V DC.
The permanent rated current (Iu) is 35 A, and the operational current at 40°C is also 35 A.
According to IEC standards, the breaking capacity (Icu) is 55 kA at 240 V, 36 kA at 415 V, and 5 kA at 690 V. According to UL standards, the breaking capacity is 65 kA at 240 V and 25 kA at 480 V.
This circuit breaker is designed for DIN rail mounting.
The RoHS status is RoHS3 Compliant, and the REACH status is REACH Unaffected.