This Siemens 3VA5 series molded-case circuit breaker, part number 3VA5135-4ED26-0AA0, is engineered for reliable system protection. It features a 2-pole configuration and a rated operational current of 35A at 40°C, with derated values at higher temperatures.
The breaker provides a significant breaking capacity of 25kA at 480V according to UL 489 standards, and 36kA at 415V according to IEC 60947. It is equipped with TM210 overcurrent release with LI protection function, offering overload and fixed short-circuit protection.
Designed for convenient installation, this circuit breaker supports DIN rail mounting and features a lever actuator. It operates with an insulation voltage of 600V and a rated AC operating voltage of 415V. The device also includes HACR and HID type ratings, making it suitable for various applications in HVAC and high-intensity discharge lighting systems.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 35A at 40°C, derating to 32A at 70°C.
The breaking capacity is 25kA at 480V according to UL 489, and 36kA at 415V according to IEC 60947.
This circuit breaker has 2 poles.
It is designed for DIN rail mounting.
The rated AC operating voltage is 415V, and the maximum DC operational voltage is 250V.
It features TM210 overcurrent release with LI protection for overload and fixed short-circuit protection.