| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating | |
| Width |
The Siemens 3VA5135-4ED12-0AA0 is a 1-pole molded-case circuit breaker from the SENTRON series, designed for system protection applications. It features a rated insulation voltage of 500V and a maximum operational voltage of 415V AC.
This circuit breaker has an operational current rating of 35A at 40°C, with derated values at higher temperatures. It offers a breaking capacity of 25kA at 240V and 5kA at 415V according to IEC 60947 standards, and 65kA at 120V and 25kA at 277V according to UL 489 standards. The overcurrent release is of type TM210 with LI protection function.
With a mechanical service life of 20,000 switching cycles and electrical endurance ratings of 8,000 cycles at 380/415V, this breaker is built for durability. It is designed for front connection and DIN rail mounting. The dimensions are 140mm in height, 25.4mm in width, and 76.5mm in depth.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current is 35A at 40°C, derating to 32A at 70°C.
The rated insulation voltage is 500V, and the rated operational voltage at AC is 415V.
According to IEC 60947, the breaking capacity is 25kA at 240V and 5kA at 415V. According to UL 489, it is 65kA at 120V and 25kA at 277V.
This circuit breaker is designed for DIN rail mounting.
The typical mechanical service life is 20,000 switching cycles.