| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
The Siemens 3VA5135-4EC41-0AA0 is a 4-pole molded-case circuit breaker from the 3VA5 series, designed for system protection applications. It operates with a rated current of 35A and offers a breaking capacity of 25kA at 480V, conforming to UL 489 standards.
This circuit breaker features a TM230 overcurrent release with LI protection functionality. It has an insulation voltage of 800V and a maximum operational voltage of 690V AC or 600V DC. The device is suitable for HACR type applications and mounts via DIN rail.
With a mechanical service life of 15,000 switching cycles and electrical endurance ratings of up to 8,000 cycles at 480V, the 3VA5135-4EC41-0AA0 is built for reliability. It has a frame size of 125A and an adjustable response current (Ir) of 35A, with adjustable short-circuit response (Ii) from 175A to 350A.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The permanent current rating (Iu) is 35A, with an operational current of 35A at 40°C.
The breaking capacity according to UL 489 is 25kA at 480V. According to IEC 60947, the breaking capacity (Icu) is 36kA at 415V.
The maximum rated operational voltage (Ue) is 690V AC at 50/60Hz and 600V DC.
This circuit breaker is designed for DIN rail mounting.
It features LI protection with a TM230 overcurrent release.