| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage | |
| Voltage Rating | |
| Width |
This Siemens SENTRON molded-case circuit breaker, part number 3VA5130-6ED12-0AA0, is designed for system protection applications. It features a 1-pole configuration with a rated operational current of 30A at 40°C, derating to 27A at 70°C. The circuit breaker operates at a rated voltage of 415V AC and has a maximum breaking capacity of 50kA at 277V according to UL 489 standards.
With a TM210 overcurrent release and LI protection function, this breaker provides overload and fixed short-circuit protection. It is suitable for HACR and HID type applications as per UL 489. The mechanical service life is rated at a typical 20,000 switching cycles, with electrical endurance varying based on AC-1 conditions and voltage levels.
The unit is designed for front connection and mounts via DIN rail. Its dimensions are 140mm in height, 25.4mm in width, and 76.5mm in depth. The breaker has a maximum power loss of 3.2W.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated insulation voltage is 500 V.
The maximum rated operational voltage with DC is 125 V.
The operating voltage at AC is rated at 415 V.
The maximum power loss is 3.2 W.
The typical mechanical service life is 20,000 switching cycles.
The operational current at 40°C is 30 A.
The breaking capacity current at 277 V is 50 kA.
The mounting type is DIN Rail.