3VA5130-5ED31-0AA0 The Siemens 3VA5130-5ED31-0AA0 is a 3-pole molded-case circuit breaker rated for 30A and 690V. It features a breaking capacity of 35kA at 480V.
Mfr Part #:

3VA5130-5ED31-0AA0

Mfr Name: Siemens
Siemens
The Siemens 3VA5130-5ED31-0AA0 is a 3-pole molded-case circuit breaker rated for 30A and 690V. It features a breaking capacity of 35kA at 480V.
Stock on Request

3VA5130-5ED31-0AA0 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Current Rating
Current Rating (Amps)
Height
Illumination
Mounting Type
Number of Poles
Voltage Rating

3VA5130-5ED31-0AA0 Description

Short technical summary and product information.

The Siemens 3VA5130-5ED31-0AA0 is a 3-pole molded-case circuit breaker from the SENTRON series, designed for system protection. It operates with a rated current of 30A at 40°C and a maximum rated operational voltage of 690V AC.

 

This circuit breaker offers a breaking capacity of 35kA at 480V according to UL 489 standards and 85kA at 240V according to IEC 60947. The overcurrent release type is TM210 with LI protection function. It is suitable for HACR Type applications.

 

With a mechanical service life of 15,000 cycles and electrical endurance ratings of up to 8,000 cycles, this breaker is built for durability. It is designed for DIN rail mounting and has compact dimensions of 140mm height, 76.2mm width, and 76.5mm depth.

3VA5130-5ED31-0AA0 Quick Information

Product Type: Circuit Breaker
Series: 3VA51
Canonical Name: Siemens 3VA5 Molded-case Circuit Breaker

3VA5130-5ED31-0AA0 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3VA5130-5ED31-0AA0 Features

  • 3-pole molded-case circuit breaker
  • Rated for 30A operational current
  • Maximum 690V AC operational voltage
  • 35kA breaking capacity at 480V (UL 489)
  • DIN rail mounting type

3VA5130-5ED31-0AA0 Applications

  • System protection applications
  • Suitable for HACR Type loads
  • Industrial control panels
  • Power distribution systems

3VA5130-5ED31-0AA0 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the rated voltage of this circuit breaker?

The maximum rated operational voltage is 690 V AC (50/60 Hz) and 500 V DC, with an insulation voltage of 800 V.

What is the rated current and how does it vary with temperature?

The rated current is 30 A at 40°C ambient. It derates to 29.4 A at 45°C, 28.8 A at 50°C, 28.3 A at 55°C, 27.7 A at 60°C, 27.2 A at 65°C, and 26.7 A at 70°C.

What are the short-circuit breaking capacities?

Icu (maximum short-circuit breaking capacity): 85 kA at 240 V, 55 kA at 415 V, 7 kA at 690 V. Ics (operating short-circuit breaking capacity): 110 kA at 240 V, 55 kA at 415 V, 5 kA at 690 V.

What type of overcurrent release does this breaker have?

It has a TM210 thermal-magnetic overcurrent release providing LI (long-time and instantaneous) protection.

What are the dimensions and mounting method?

The breaker is designed for DIN Rail mounting. Dimensions are 140 mm height, 76.2 mm width, 76.5 mm depth.

Is this breaker HACR rated?

Yes, it is designated as HACR Type (Heating, Air Conditioning, and Refrigeration) per UL 489.

What agency approvals does it have?

It is approved by CCC, CE, CSA, UL489, and VDE.