| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating | |
| Width |
The Siemens 3VA5125-6ED12-0AA0 is a 1-pole molded-case circuit breaker designed for system protection. It features an operational current of 25A at 40°C, with a derated current of 22A at 70°C. The rated insulation voltage is 500V, and the maximum rated operational voltage for DC is 125V, while the rated operational voltage for AC is 415V.
This circuit breaker offers a breaking capacity of 50kA at 277V according to UL 489 standards, and 5kA at 415V according to IEC 60947 standards. It includes overload protection with Ir=25A and fixed short-circuit protection with Ii=12 x In. The device is suitable for HACR and HID type applications.
With a mechanical service life of 20,000 switching cycles and electrical endurance of 8,000 cycles at 380/415V, it is built for durability. The circuit breaker has a net weight of 0.407 kg and is designed for DIN rail mounting. Its dimensions are 140mm in height, 25.4mm in width, and 76.5mm in depth.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum operating voltage is 415 V AC.
The current rating is 25A.
The breaking capacity at 415V is 5 kA.
It has a mechanical service life of 20,000 switching cycles.
It mounts on a DIN rail.