| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating | |
| Width |
This Siemens 3VA5120-6ED22-0AA0 is a 2-pole molded-case circuit breaker from the SENTRON series, designed for system protection. It offers a rated operational current of 20A at 40°C and a breaking capacity of 65kA at 480V according to UL 489 standards.
The circuit breaker features a TM210 overcurrent release with LI protection, providing overload and fixed short-circuit protection. It is suitable for HACR, HID, and SWD type applications under UL 489.
With a mechanical service life of 20,000 switching cycles and electrical endurance ratings up to 8,000 cycles at 415V, this breaker is built for durability. It has a rated insulation voltage of 600V and a maximum operational voltage of 250V DC. The unit is designed for DIN rail mounting and has front connections for the main current circuit.
Key electrical specifications include a maximum power loss of 8.13W and an active power loss per pole of 4.07W. The dimensions are 140mm in height, 50.8mm in width, and 76.5mm in depth.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 20A at 40°C and 45°C, decreasing slightly at higher temperatures.
The breaking capacity is 65kA at 480V according to UL 489 standards, and 70kA at 415V according to IEC 60947.
It features TM210 overcurrent release with LI protection for overload and fixed short-circuit protection.
The dimensions are 140mm in height, 50.8mm in width, and 76.5mm in depth.
The RoHS status is listed as RoHS3 Compliant.
The Moisture Sensitivity Level (MSL) is 1 Unlimited.