| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
This Siemens 3VA5111-5GC41-0AA0 is a 4-pole molded-case circuit breaker from the 3VA5 series, designed for system protection. It features a permanent rated current of 110A, with operational current ratings varying based on ambient temperature, down to 98.2A at 70°C.
The breaker provides a maximum rated operational voltage of 690V AC and 600V DC, with an insulation voltage of 800V. Its breaking capacity according to UL 489 is 35kA at 480V and 18kA at 600Y/347V. According to IEC 60947, the breaking capacity (Icu) is 55kA at 415V and 7kA at 690V. The short-circuit current making capacity (Icm) is 121kA at 415V and 11.9kA at 690V.
Adjustable overcurrent protection includes overload protection (Ir) set at a minimum of 110A and short-circuit protection (Ii) adjustable from 550A to 1100A. The N-conductor protection is designed for 100% capacity. The breaker has a mechanical service life of typically 15,000 switching cycles and electrical endurance ratings of up to 8,000 cycles at 380/415V.
Designed for DIN rail mounting, this circuit breaker is suitable for applications requiring robust overcurrent protection. It is compliant with UL 489 standards and carries multiple agency approvals including CCC, CE, CSA, EAC, and VDE.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage for this circuit breaker is 690 V with AC 50/60Hz and 600 V with DC.
The breaking capacity according to UL 489 at 480 V is 35 kA.
The permanent rated current (Iu) is 110 A.
This circuit breaker has 4 poles.
This circuit breaker supports DIN Rail mounting.