| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Overload Protection | |
| Voltage | |
| Voltage Rating |
This Siemens 3VA5 molded-case circuit breaker, part number 3VA5111-5ED36-1AA0, is a 3-pole device designed for system protection applications. It features a rated operating voltage of 690V AC and a nominal current rating of 110A at 40°C, with derated values specified up to 70°C.
The circuit breaker provides a breaking capacity of 35kA at 480V, 85kA at 240V, and 18kA at 600Y/347V. It incorporates TM210 overcurrent release with LI protection function and fixed short-circuit protection set at 10 x In. Overload protection is set at Ir=110A.
With a mechanical service life of typically 20,000 switching cycles and electrical endurance ratings of 8,000 cycles at 380/415V and 4,000 cycles at 690V, this breaker is built for durability. It is HACR Type compliant and mounts via DIN rail.
Additional specifications include a maximum power loss of 25.8W and an active power loss of 8.6W per pole. The net weight is 0.951 kg.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage is 690 V AC.
The operational current at 40°C is 110 A.
The breaking capacity at 480V is 35 kA.
This circuit breaker has 3 poles.
It offers LI protection function for the overcurrent release.
The mounting type is DIN Rail.