| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating | |
| Current Rating (Amps) | |
| Depth | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Overload Protection | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating | |
| Width |
This Siemens 3VA5110-5ED11-0AA0 is a 1-pole molded-case circuit breaker designed for system protection. It features a permanent rated current (Iu) of 100A and a maximum rated operational voltage of 415V AC at 50/60Hz, with a DC operational voltage of 125V.
The circuit breaker has a breaking capacity of 36 kA at 240V and 5 kA at 415V according to IEC 60947 standards. Under UL 489 standards, it provides a breaking capacity of 85 kA at 120V, 35 kA at 277V, and 18 kA at 347V. The overcurrent release type is TM210 with LI protection function.
With a mechanical service life of typically 15,000 switching cycles and electrical endurance ratings of 8,000 cycles at 380/415V and 4,000 cycles at 690V, this breaker is built for durability. It is designed for DIN rail mounting and has dimensions of 140 mm height, 25.4 mm width, and 76.5 mm depth.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The maximum rated operational voltage for this circuit breaker is 415 V with AC 50/60Hz and 125 V with DC.
The breaking capacity at 277V according to UL 489 is 35 kA.
The permanent rated current (Iu) is 100 A.
This circuit breaker is designed for DIN Rail mounting.
The dimensions are 140 mm in height, 25.4 mm in width, and 76.5 mm in depth.